Halogen Free Cable
H05Z1-K & H07Z1-K
Brand: RR Kable
Application
Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. For use in public places such as: hospitals, schools, museums, airports, bus terminals, shops in general, etc., as well as in computer rooms, offices, production plants, switchboard wiring, laboratories, etc.
Standard
BS EN 50525-3-31.
Cable Construction
Conductor Class 5 flexible plain / metal coated stranded according to EN 60228.
Insulation of thermoplastic halogen-free compound type TI7 to EN 50363-7.
Properties
- Smoke density to acc. to EN 61034-2.
- Halogen free acc. to EN 50525-1, EN 60754-1.
- Corrosivity acc. to EN 60754-2.
- Ozone resistant according to EN 60811-2-1 or HD 505.2.1.
- Self-extinguishing and flame retardant according to EN 60332-1-2.
- LSOH = Low Smoke Zero Halogen.
Technical Data
- Nominal Voltage : H05Z1- K Uo / U 300 / 500V; H07Z1- K Uo / U 450 / 750V
- Harmonized Designation : 0.5 mm² to 1 mm² – H05Z1- K, 1.5 mm2 to 240 mm2 – H07Z1- K
- Temperature Range : -30°C to +70°C
- Minimum Bending Radius :
Cable diameter ≤ 8 mm: 4 x outer diameter
Approx. diameter > 8 to 12 mm: 5 x outer diameter
Approx. diameter > 12 mm: 6 x outer diameter
- Test Voltage: 2500V
Related Product

Halogen-Free H07Z-R-6491B
- Uo / U – 450 / 750V
- 1.5 mm² to 630 mm² stranded class 2 – H07Z-R
- -15°C to 90°C

H05Z1Z1-F (318B)
- U / U 300/500 V
- Flexing -5°C to +70°C. Fixed Installation : -30°C to +70°C
- Flexing 7.5 x cable ø; Fixed installation 4 x cable ø