Data Cable

LIYY

Brand: RR Kable

Technical Data

  • Standard: Based on VDE 0812
  • Voltage Grade (Not for power installation) : 0.14 mm² = 350 V; >/= 0.25 mm² = 500 V
  • Insulation Resistance: Min. 20 GΩ x cm
  • Temperature Range : Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
  • Minimum Bending Radius: For flexible use 10 x cable ø
  • Test Voltage: Up to 0.25 mm² = 1200 V. From 0.34 mm² = 2000 V
  • Breakdown Voltage: Up to 0.25 mm² = 2400 V. From 0.34 mm² = 4000 V

Cable construction

  •  Bare copper, fine wire conductors stranded according to DIN VDE 0295/ EN 60228 cl. 5,
  •  Special PVC core insulation TI2, to EN 50363-3.
  •  Conductor make-up for

 0.14 mm² = 18 x 0.10 mm.

 0.25 mm² = 14 x 0.15 mm.

 0.34 mm² = 19 x 0.15 mm.

  •  Core colours as per DIN 47100 (Refer table no. 2-2).
  •  Cores stranded in layers with optimal lay-length.
  •  Plastic foil wrapping for 10 cores and above.
  •  Special PVC outer sheath TM2, to EN 50363-4.1.
  •  Colour grey (RAL 7032).

Properties

  • PVC self-extinguishing and flame retardant according to EN 60332-1-2.
  • Capacitance (approx. Value)
  • up to 0.5 mm² – 120 nF/km
  • above 0.5 mm² – 160 nF/km.
  • Inductance approx. 0.65 mH/km.

Related Product

RR Kable

LIYY (TP)

  • PVC self-extinguishing and flame retardant according to EN 60332-1-2.
  • LiYY (TP) is applicable in the short runs and tight spaces, where the main requirements are smaller outer diameter and bending radii. The cable ideally meets these requirements.